Sensor and Controller Catalog
Product Selection Guide
Power Switching Devices
Other
Firing
Configurations Inputs
Phase
Output
Maximum Current
Operating Range °C
Features
Ambient
Mounting
Dimensions
°F
Connectivity
Closed Loop
V, I, P Contol
Data Logging
ASPYRE ® AT
No Modbus ® RTU, Watlow Intermodule
48A 1 1 analog (0-10VDC or 4-20mA) 2 digital
Zero-cross, Burst firing, Phase angle, Soft start
Yes
DIN-rail, back panel, cooling plate
High accuracy V.I.P. measure- ment, Heater bakeout OLED display, Heater bakeout
32 to 140
0 to 60
6.68 in. H x 1.59 in. W x 5.93 in. D (24A) or 7.15 in. D (48A)
Bus, USB port for config up/ download
ASPYRE DT
2400A 1 or 3
2 analog (0-5VDC or 4-20mA) 2 digital
Zero-cross, Single cycle, Burst firing, Phase angle, Delayed triggering
Yes Profibus DP, Modbus ® RTU, Modbus ® TCP (Ethernet), ProfiNet, USB port for
Yes
Back panel
32 to 140
0 to 60
4.77 in. H x 2.84 in. W x 7.28 in. D (smallest) to 20.47 in. H x 10.32 in. W x 10.63 in. D (largest)
config up/ download
See page 24 5
DIN-A-MITE ® A
25A 1 VAC/VDC contactor, 4-20mA
Zero-cross
No
No
No DIN-rail, back panel
— 0 to 176
-18 to 80
3.7 in. H x 1.8 in. W x 3.9 in. D
(95 mm H x 45 mm W x 98 mm D)
See page 25 2
DIN-A-MITE B
40A 1 or 3
VAC/VDC contactor, 4-20mA, multi-zone input
Zero-cross
No
No
No DIN-rail, back panel
Shorted SCR alarm
0 to 176
-18 to 80
3.7 in. H x 3.1 in. W x 4.9 in. D
(95 mm H x 80 mm W x 124 mm D)
See page 25 5
DIN-A-MITE C
80A 1 or 3
VAC/VDC contactor, 4-20mA, multi-zone input, linear voltage, potentiom- eter
Zero-cross, phase angle
No
No
No DIN-rail, through wall, back panel
Shorted SCR alarm, open heater alarm on zero-cross, current limit
0 to 176
-18 to 80
DIN-rail mount, without fan: 5.45 in. H x 3.25 in. W x 5.89 in. D (138 mm H x 83 mm W x 150 mm D)
See page 25 8
DIN-A-MITE D
100A 1 VAC/VDC contactor, 4-20mA
Zero-cross
No
No
No Back panel
Shorted SCR alarm, load
0 to 176
-18 to 80
7.25 in. H x 2.5 in. W x 9.4 in. D (185 mm H x
current monitor
65 mm W x 240 mm D)
See page 26 4
Solid State Relays (SSR)
75A 1 VAC/VDC contactor
Zero-cross, random fire
No
No
No Back panel
Shorted SSR alarm, 20A DC output, 4 to 20mA dc variable time base firing
-40 to 185
-40 to 85
Without heat sink: 2.25 in. H x 1.75 in. W x 0.9 in. D (57.2 mm H x 44.5 mm W x 23 mm D)
See page 26 7
16 5
Made with FlippingBook HTML5